Show simple item record

AuthorAhmed, K. H.
AuthorMassoud, Ahmed
AuthorFinney, S. J.
AuthorWilliams, B. W.
Available date2022-03-23T07:01:10Z
Publication Date2011
Publication NameInternational Conference on Power Engineering, Energy and Electrical Drives
ResourceScopus
Identifierhttp://dx.doi.org/10.1109/PowerEng.2011.6036430
URIhttp://hdl.handle.net/10576/28869
AbstractThis paper proposes a synchronous DQ frame current controller for inverter based interfaced systems. The grid voltage may be unbalanced, possibly due to unequal line impedance. The output active and reactive powers oscillate at twice the fundamental grid frequency around the desired values, due to the negative sequence voltage. The proposed controller can eliminate the effect of the negative sequence component, using two separate PI controllers. The first is associated with positive sequence current control and the other is for the negative sequence. A modified phase locked loop is proposed and confirmed practically. Steepest descent adaptive control for grid voltage estimation is employed in the control system. The proposed controller produces high quality current injected into the grid, therefore, high power quality. Simulated and practical results verify the performance of the proposed control system.
Languageen
PublisherIEEE
SubjectAdaptive Control
Current controller
Dq-frame
Grid frequency
Grid voltage
High power quality
High quality
Inverter-based
Line impedance
Negative sequence
Negative sequence voltage
PI Controller
Sequence current
Steepest descent
Three-phase voltages
Adaptive control systems
Electric current control
Power quality
Controllers
TitleA synchronous DQ frame controller via an LCL coupled filter under unbalanced three-phase voltage supply conditions
TypeConference Paper


Files in this item

FilesSizeFormatView

There are no files associated with this item.